- Overview
- Specifications
- Downloads
![]()
Heating/Cooling 15 to 75 Tons
![]()
Overview
System performance and reliability make Daikin McQuay Maverick II commercial packaged rooftop systems the ideal solution for new, retrofit or replacement applications on one to three-story buildings. Available in capacities from 15 to 70 tons, they combine the lower installation costs and interior space savings of a roof-mounted system with the operating and maintenance efficiencies of central heating and cooling systems.Applications range from offices and schools to libraries and strip malls. Arriving at your job site as a complete package, Maverick II commercial rooftop systems maximize your design and installed cost savings. They also can add to your building’s profit margins year after year with efficient, reliable performance, and a wide array of features and benefits:
- VAV or constant volume operation
- Non-ozone depleting R-410A refrigerant
- Optional energy heat recovery wheel for increased air conditioning capacity
- Double wall construction protects insulation
- Low leak damper meet ASHRAE standard 90.1
- AF fans for efficient operation
- Stainless steel drain pan for improved IAQ
- Building pressure control option for exhaust fan
- Controls flexibility—MicroTech®III controls with our Open Choices™ feature for easy integration with the BAS of your choice
- Optional hot gas reheat for dehumidification control
Physical Data - MPS 0015 through 026
| Model | MPS | ||||
|---|---|---|---|---|---|
| 015 ton | 017 ton | 020 ton | 026 ton | ||
| Cooling performance | |||||
| Gross cooling capacity (tons) | 16.0 | 18.5 | 21.7 | 25.3 | |
| Nominal airflow (cfm) | 6000 | 7000 | 8000 | 10,000 | |
| Maximum EER | 11.0 - 11.1 | 11.0 - 11.2 | 10.0 | 10.8 | |
| Maximum IEER | 11.2 - 11.5 | 11.2 - 12.0 | 11.2 | 12.8 | |
| Gas Heating Performance | |||||
| Low heat MBH (input/output)1 | 240/192 | 240/192 | 240/192 | 240/192 | |
| Number of stages (low heat) | 2 | 2 | 2 | 2 | |
| Turndown (low heat)2 | 4:1 | 4:1 | 4:1 | 4:1 | |
| Gas connection pipe size/qty (low heat) | 3/4"/1 | 3/4"/1 | 3/4"/1 | 3/4"/1 | |
| High heat MBH (input/output)1 | 480/384 | 480/384 | 480/384 | 480/384 | |
| Number of stages (high heat) | 4 | 4 | 4 | 4 | |
| Gas connection pipe size/qty (high heat) | 3/4"/2 | 3/4"/2 | 3/4"/2 | 3/4"/2 | |
| Turndown (high heat)2 | 8:1 | 8:1 | 8:1 | 8:1 | |
| Steady state efficiency | 80% | 80% | 80% | 80% | |
| Hot Water Heating Performance | |||||
| Face area (sq ft) | 12.2 | 12.2 | 12.25 | 12.25 | |
| Rows/FPI (low heat) | 1/11 | 1/11 | 1/14 | 1/14 | |
| Coil model (low heat) | 5WB | 5WB | 5WB | 5WB | |
| Connection sizes/type (low heat)2 | ODM Sweat | ODM Sweat | ODM Sweat | ODM Sweat | |
| Rows/FPI (high heat) | 2/12 | 2/12 | 2/9 | 2/9 | |
| Coil model (high hea | 5WB | 5WB | 5WS | 5WS | |
| Connection sizes/type (high heat)2 | ODM Sweat | ODM Sweat | ODM Sweat | ODM Sweat | |
| Electric Heating Performance | |||||
| Number of stages | 4 | 4 | 4 | 4 | |
| kW (low/medium/high heat) | 18/36/54 | 18/36/54 | 36/54/72 | 36/54/72 | |
| Compressors | |||||
| Type/number | Scroll/2 | Scroll/2 | Scroll/2 | Scroll/2 | |
| Number of stages | 2 | 2 | 4 | 4 | |
| Evaporator Coils | |||||
| Rows | 4 | 4 | 4 | 4 | |
| FPI | 14 | 14 | 13 | 13 | |
| Face area (sq ft) | 18.2 | 18.2 | 18.2 | 18.2 | |
| Capacity control | TxV | TxV | TxV | TxV | |
| Hot Gas Reheat | |||||
| Coil type | Microchannel | Microchannel | Microchannel | Microchannel | |
| Control type | Modulating | Modulating | Modulating | Modulating | |
| Face area (sq ft) | 14.1 | 14.1 | 14.1 | 14.1 | |
| Condenser Coils | |||||
| Fin type | Enhanced | Enhanced | Enhanced | Enhanced | |
| FPI | 18 | 18 | 18 | 18 | |
| Face area (sq ft) | 18.1 | 18.1 | 18.1 | 18.1 | |
| Outdoor Fans | |||||
| Type | Propeller | Propeller | Propeller | Propeller | |
| Number - diameter | 2 - 26" | 2 - 26" | 2 - 26" | 2 - 26" | |
| Drive type/number of speeds | Direct/1 | Direct/1 | Direct/1 | Direct/1 | |
| Indoor Fans | |||||
| Type | AF - SWSI | AF - SWSI | AF - SWSI | AF - SWSI | |
| Number - diameter | 1 - 18" | 1 - 18" | 1 - 20" | 1 - 22" | |
| Drive type | Fixed sheave | Fixed sheave | Fixed sheave | Fixed sheave | |
| Isolation | 1" spring | 1" spring | 1" spring | 1" spring | |
| Number of motors | 1 | 1 | 1 | 1 | |
| Motor hp range | 1.5 - 10 | 1.5 - 10 | 2 - 15 | 2 - 15 | |
| Motor nominal rpm | 1800 | 1800 | 1800 | 1800 | |
| Motor efficiency | Premium | Premium | Premium | Premium | |
| Filters | |||||
| Type | 2", MERV 7 | ||||
| Area (sq ft) | 24 | 24 | 24 | 24 | |
| Qty. - size | 6 - 24" x 24" | ||||
| Total Unit Weight | |||||
| Weight (lbs) | Cooling | Cooling | Cooling | Cooling | |
| 2650 | 2700 | 2955 | 3055 | ||
| Curb | |||||
| Height | 14" - 24" | 14" - 24" | 14" - 24" | 14" - 24" | |
| Weight (lbs) | 341 - 501 | 341 - 501 | 341 - 501 | 341 - 501 | |
- Piping connections are given with a male outside diameter dimension, brazed connection.
- Modulating burner only.
- Base unit weight includes Economizer, VFDs, and the smallest supply fan available. Heating units include maximum gas heat.
Physical Data - MPS 030 through 050
| Model | MPS | ||||
|---|---|---|---|---|---|
| 030 ton | 035 ton | 040 ton | 050 ton | ||
| Cooling performance | |||||
| Gross cooling capacity (tons) | 30.0 | 34.0 | 40.0 | 50.0 | |
| Nominal airflow (cfm) | 12,000 | 14,000 | 16,000 | 20,000 | |
| Maximum EER | 10.2–10.4 | 9.9–10.1 | 10.0–10.3 | 9.8–10.2 | |
| Maximum IEER | 12.2–13.1 | 11.4–12.3 | 11.8–13.2 | 11.6–12.3 | |
| Gas Heating Performance | |||||
| Low heat MBH (input/output)1 | 300/240 | 300/240 | 400/320 | 400/320 | |
| Number of stages (low heat) | 2 | 2 | 2 | 2 | |
| Turndown (low heat)2 | 4:1 | 4:1 | 4:1 | 4:1 | |
| Gas connection pipe size/qty (low heat) | 3/4"/1 | 3/4"/1 | 3/4"/1 | 3/4"/1 | |
| High heat MBH (input/output)1 | 600/480 | 600/480 | 800/640 | 800/640 | |
| Number of stages (high heat) | 4 | 4 | 4 | 4 | |
| Gas connection pipe size/qty (high heat) | 3/4"/2 | 3/4"/2 | 3/4"/2 | 3/4"/2 | |
| Turndown (high heat)2 | 8:1 | 8:1 | 8:1 | 8:1 | |
| Steady state efficiency | 80% | 80% | 80% | 80% | |
| Hot Water Heating Performance | |||||
| Face area (sq ft) | 19.25 | 19.25 | 19.25 | 19.25 | |
| Rows/FPI (low heat) | 1/12 | 1/12 | 1/11 | 1/11 | |
| Coil model (low heat) | 5WB | 5WB | 5WH | 5WH | |
| Connection sizes/type (low heat)2 | ODM Sweat | ODM Sweat | ODM Sweat | ODM Sweat | |
| Rows/FPI (high heat) | 2/10 | 2/10 | 2/13 | 2/13 | |
| Coil model (high hea | 5WS | 5WS | 5WS | 5WS | |
| Connection sizes/type (high heat)2 | ODM Sweat | ODM Sweat | ODM Sweat | ODM Sweat | |
| Electric Heating Performance | |||||
| Number of stages | 4 | 4 | 4 | 4 | |
| kW (low/medium/high heat) | 54/72/90 | 54/72/90 | 72/90/108 | 72/90/108 | |
| Compressors | |||||
| Type/number | Scroll/3 | Scroll/3 | Scroll/4 | Scroll/4 | |
| Number of stages | 5 | 5 | 5 | 5 | |
| Evaporator Coils | |||||
| Rows | 4 | 4 | 4 | 4 | |
| FPI | 12 | 12 | 12 | 12 | |
| Face area (sq ft) | 25.4 | 25.4 | 29.4 | 35.7 | |
| Capacity control | TxV | TxV | TxV | TxV | |
| Hot Gas Reheat | |||||
| Coil type | Microchannel | Microchannel | Microchannel | Microchannel | |
| Control type | Modulating | Modulating | Modulating | Modulating | |
| Face area (sq ft) | 19.9 | 19.9 | 26.8 | 26.8 | |
| Condenser Coils | |||||
| Fin type | Enhanced | Enhanced | Enhanced | Enhanced | |
| FPI | 18 | 18 | 18 | 18 | |
| Face area (sq ft) | 13.4/27.5 | 13.4/27.5 | 13.4/27.5 | 27.5 (× 2) | |
| Outdoor Fans | |||||
| Type | Propeller | Propeller | Propeller | Propeller | |
| Number - diameter | 3 - 26" | 3 - 26" | 4 - 26" | 4 - 26" | |
| Drive type/number of speeds | Direct/1 | Direct/1 | Direct/1 | Direct/1 | |
| Indoor Fans | |||||
| Type | AF - SWSI | AF - SWSI | AF - SWSI | AF - SWSI | |
| Number - diameter | 1 - 24" | 1 - 24" | 1 - 20" | 1 - 30" | |
| Drive type | Fixed sheave | Fixed sheave | Fixed sheave | Fixed sheave | |
| Isolation | 1" spring | 1" spring | 1" spring | 1" spring | |
| Number of motors | 1 | 1 | 1 | 1 | |
| Motor hp range | 5 - 20 | 5 - 20 | 7-1/2 - 30 | 7-1/2 - 30 | |
| Motor nominal rpm | 1800 | 1800 | 1800 | 1800 | |
| Motor efficiency | Premium | Premium | Premium | Premium | |
| Filters | |||||
| Type | 2", MERV 6 | ||||
| Area (sq ft) | 32 | 32 | 36 | 44 | |
| Qty. - size | 8 - 24" × 24" | 8 - 24" × 24" | 8 – 24" × 24"/4 – 18" × 24" | 8 – 24" × 24"/4 – 18" × 24" | |
| Total Unit Weight | |||||
| Weight (lbs) | Cooling | Cooling | Cooling | Cooling | |
| 3660 | 3660 | 4685 | 4985 | ||
| Curb | |||||
| Height | 14" - 24" | 14" - 24" | 14" - 24" | 14" - 24" | |
| Weight (lbs) | 341 - 501 | 341 - 501 | 481 - 501 | 481 - 501 | |
- Piping connections are given with a male outside diameter dimension, brazed connection.
- Modulating burner only.
- Base unit weight includes Economizer, VFDs, and the smallest supply fan available. Heating units include maximum gas heat.
Physical Data - MPS 062 through 075
| Model | MPS | |||
|---|---|---|---|---|
| 062 ton | 070 ton | 075 ton | ||
| Cooling performance | ||||
| Nominal gross cooling capacity (tons) | 62.0 | 70.0 | 75.0 | |
| Nominal airflow (cfm) | 24,000 | 26,000 | 28,000 | |
| Maximum EER | 10.0 - 10.3 | 9.7 | 9.3 | |
| Maximum IEER | 12.4 - 12.7 | 13.0 - 13.6 | 12.2 - 12.9 | |
| Gas Heating Performance | ||||
| Low heat MBH (input/output)1 | 500/400 | 500/400 | 500/400 | |
| Gas connection pipe size/qty (low heat) | 1"/1 | 1"/1 | 1"/1 | |
| Medium heat MBH (input/output)1 | 600/480 | 600/480 | 800/640 | |
| Gas connection pipe size/qty (medium heat) | 1 1/4"/1 | 1 1/4"/1 | 1 1/4"/1 | |
| High heat MBH (input/output)1 | 980/790 | 980/790 | 980/790 | |
| Gas connection pipe size/qty (high heat) | 1 1/4"/1 | 1 1/4"/1 | 1 1/4"/1 | |
| Number of stages - all furnaces (high heat) | Mod | Mod | Mod | |
| Turndown (high heat)2 | 3:1 | 3:1 | 8:1 | |
| Steady state efficiency | 80% | 80% | 80% | |
| Hot Water Heating Performance | ||||
| Face area (sq ft) | 29.7 | 29.7 | 29.7 | |
| Type - rows (standard / high capacity) | 5WH - 1 / 5WS - 2 | 5WH - 1 / 5WS - 2 | 5WH - 1 / 5WS - 2 | |
| FPI | 9 | 9 | 9 | |
| Electric Heating Performance | ||||
| Number of stages | 4 | 4 | 4 | |
| kW (low/medium/high heat) | 100/120/160 | 100/120/160 | 100/120/160 | |
| Compressors | ||||
| Type/number | Scroll/4 | Scroll/6 | Scroll/6 | |
| Number of stages | 4 | 6 | 6 | |
| Evaporator Coils | ||||
| Rows | 5 | 5 | 5 | |
| FPI | 10 | 10 | 10 | |
| Face area (sq ft) | 39.5 or 47.1 | 47.1 | 47.1 | |
| Capacity control | TxV | TxV | TxV | |
| Outdoor Fans | ||||
| Type | Propeller | Propeller | Propeller | |
| Number - diameter | 6 - 26" | 6 - 26" | 6 - 26" | |
| Drive type/number of speeds | Direct/1 | Direct/1 | Direct/1 | |
| Indoor Fans | ||||
| SWSI AF | AF - SWSI | |||
| DWDI AF | 1 - 24" | |||
| Drive type | Fixed sheave | |||
| Isolation | 2" spring | |||
| Number of motors | 1 | |||
| Motor hp range | 5 - 20 | |||
| Motor nominal rpm | 1800 | |||
| Motor efficiency | Premium | |||
| Filters | ||||
| Qty. - type / sq. ft. | (7) 16 x 20 and (21) 16 x 25 / 73 sq. ft. | |||
| Area (sq ft) | Merv 6 angular: 6" Merv 11 or 12" Merv 14: | |||
- Heating output is for standard conditions at sea level.
- Modulating burner only.
Control
BACnet® Communication Module Configuration Tool Version 1.10 for Maverick™ Rooftop Unit only (10/08) - (166K) (Pub: 2008/10/03)
Models:MPSSoftware file of the BACnet communication module configuration tool for the 30 to 50-ton Maverick II commercial packaged rooftop unit.Control
Metric CSV File for Maverick II™ BACnet® Communication Module - (5K) (Pub: 2008/12/05)
Models:MPSMetric CSV file is required for reading metric values via BACnet from the Maverick II (MPS) commercial rooftop unit controller BACnet communication module. The metric CSV file is used in conjunction with the Maverick II BACnet configuration tool. Refer to UM 855, MicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers, for additional information.
Unit
A/SP 31-242 R-410A Rooftop Systems with 2010 Efficiencies, Competitive Pricing - (245KB) (Pub: 2008/03/25)
Models:MPS,R,RCS,RPSThe most complete line in the industry of rooftop products, 30 tons or larger, that use R-410A refrigerant. And they all offer 2010 efficiencies for lower operating costs.Unit
A/SP 31-248 R-410A Rooftop Systems Brochure - (1,136KB) (Pub: 2008/06/30)
Models:MPS,RDE,RDT,RPEMaverick II Commercial and RPS RDT Applied Rooftop Systems with R-410A refrigerant.Unit
A/SP 31-291 Maverick II Commercial Rooftop Systems - (1,343KB) (Pub: 2010/02/01)
Models:MPSMPS models 15 to 75 tons with R410A and Microtech III Unit ControllerUnit
A/SP 31-293 100% Outdoor Air Systems Brochure - (1,407KB) (Pub: 2010/03/30)
Models:MPS,RPS100% OA for Applied Rooftops 15 - 140 tons and Commercial Rooftops 15 - 50 tonsUnit
A/SP 31-314 Maverick I Commercial Packaged Rooftop Systems 3-25 Tons - (847KB) (Pub: 2010/08/04)
Models:MPSMaverick I (3 to 25 tons)with DDC controllerUnit
ASP 31-255: Ad Reprint - Now you can run with R-410A - (738KB) (Pub: 2008/11/10)
Models:MPS,RDT,RPSReprint of ad and advertorial running in trade publications, online and in e-newsletters, describing our full line of 3 to 140 ton rooftops with 2010 EERs. #AAASP31255QQ.Unit
DOAS-VRV System Brochure, ASP 31-335 - (886KB) (Pub: 2012/04/13)
Models:DPS,MPS,RPS,SWP,SWTBrochure on combining Daikin McQuay dedicated outdoor air system (DOAS) equipment with Daikin variable refrigerant volume (VRV) equipment.Control
A/SP 31-213 MD Variable Frequency Drives - (147KB) (Pub: 2007/07/05)
Models:MPS,RAH,RDE,RDR,RDS,RPE,RPS,SWP,SWTVariable frequency drives created specifically for HVAC applications.Control
A/SP 31-259 MicroTech III Remote User Interface for Rooftop and Self-Contained Systems - (391KB) (Pub: 2008/12/15)
Models:MPS,RCS,RDT,RFS,RPS,SWP,SWTThe front page of this flyer promotes the benefits of this option, while the back describes the installation and application in detail.Control
ASP 31-260 Open Choices™ for MicroTech® III Rooftop and Self Contained Systems - (541KB) (Pub: 2010/03/31)
Models:MPS,RCS,RDE,RDS,RPE,RPS,SWP,SWTBrochure detailing the capabilities and communication points on applied rooftops, Maverick™ II commercial rooftops, and self-contained systems with MicroTech III unit controllers and the Open Choices featureAccessory
A/SP 31-292 Modulating Hot Gas Reheat Option for Rooftop Systems(05-12) - (837KB) (Pub: 2012/05/01)
Models:MPSSystems with MHGRH option provide at least 15 to 20 degrees of reheat at design and excellent discharge air control, with key features that the competition cannot match.
Unit
CAT 250-7 Maverick II Commercial Packaged Rooftop Systems - (6,042KB) (Pub: 2012/02/06)
Models:MPSMaverick II Heating and Cooling units, Models MPS015F-017F, MSP020G-026G and MPS030F-050F, 15 to 75 tons, R410A Refrigerant and MicroTech III Unit Controller.Unit
CAT 253-1 Maverick I Commercial Packaged Rooftop Systems: 3 to 25 Tons - (15,985KB) (Pub: 2012/02/29)
Models:MPSMaverick I Heating and Cooling units, Models MPS003B through 025B, 3 to 25 tons.
Control
ED 15102-4 Maverick II Rooftop MicroTech II Unit Controller Protocol Information - (1,436KB) (Pub: 2012/05/18)
Models:MPSProtocol information for Maverick II commercial rooftop with MicroTech II unit controllers using BACnet or LonWorks network communications.Control
ED 15112-10 BACnet® and LonWorks® Protocol Information for MicroTech® III Rooftop and Self-Contained Units - (3,078KB) (Pub: 2012/05/18)
Models:DPS,MPS,RAH,RDE,RDS,RDT,RFS,RPE,RPS,SWP,SWTBACnet and LonWorks network protocol information for Rooftop and Self-Contained Units with MicroTech III unit controllersControl
ED 15113-4 BACnet PICS for MicroTech III Applied Air Handlers - (164KB) (Pub: 2012/04/24)
Models:DPS,MPS,RAH,RCS,RDS,RDT,RFS,RPE,RPS,SWP,SWTBACnet protocol implementation conformance statement (PICS) for Applied Air Handling Units with MicroTech III unit controllersControl
ED 15126 PICS for Maverick I Commercial Rooftop - (53KB) (Pub: 2010/06/09)
Models:MPSProtocol implementation and conformance statement (PICS) for Maverick I Commercial RootopControl
IM 999-1 Maverick I Commercial Rooftop with LonWorks SCC Module - (1,169KB) (Pub: 2011/06/07)
Models:MPSinstallation manual on the Maverick I commercial rooftop unit controller with LonWorks SCC communication module.Control
LonWorks XIF-NXE and Resource Files for Maverick I Commercial Rooftop - (18KB) (Pub: 2010/06/09)
Models:MPSLonWorks eXternal Interface File (XIF)-NXE and Resource Files for Maverick I Commercial RooftopControl
LonWorks® eXternal Interface Files for SCC Functional Profile Version 01A for MicroTech® III Applied Air Unit Controllers - (11KB) (Pub: 2008/11/03)
Models:MPS,RAH,RCE,RCS,RDE,RDS,RDT,RFS,RPE,RPS,SWP,SWTSpace Comfort Control XIF/NXE and Resource Files for MicroTech III LonMark-certified Applied Air (rooftop and self-contained) and Commercial Rooftop (Maverick II) unit controllers (MTIIIAHUSCC.zip)Control
LonWorks® eXternal Interface Files for DAC Functional Profile Version 01A for MicroTech® III Applied Air Unit Controllers - (15KB) (Pub: 2009/02/26)
Models:MPS,RCS,RDE,RDS,RDT,RFS,RPS,SWP,SWTDischarge Air Controller XIF/NXE and Resource Files for MicroTech III LonMark-certified applied air (rooftop and self-contained)and Commercial Rooftop (Maverick II) unit controllers (MTIIIAHU_DischargeAir.zip)Control
OM 1077 Maverick I DDC Rooftop Unit Controller - (3,091KB) (Pub: 2010/08/16)
Models:MPSHeating and Cooling, Gas/Electric and Electric/Electric, Models MPS 003B to 025B, 3 to 25 Tons with R410A Refrigerant
Unit
IM 1058-2 Maverick II Commercial Packaged Rooftop System MPS 015F - 050F - (7,645KB) (Pub: 2011/05/13)
Models:MPSHeating and Cooling Models MPS015F - MPS050F, 15 to 50 tons, with R-410A Refrigerant and MicroTech III Unit Controller, Energy RecoveryUnit
IM 970-1 Maverick I Commercial Packaged Rooftop Systems: 3 to 5 Tons - (6,077KB) (Pub: 2010/07/07)
Models:MPSMaverick I Heating and Cooling units, Models MPS003B through 005B, 3 to 5 tons.Unit
IM 971-1 Maverick I Commerical Packaged Rooftop Systems: 6 to 12 tons - (7,661KB) (Pub: 2010/07/07)
Models:MPSMaverick I Heating and Cooling units, Models MPS006B through 012B, 6 to 12 tons.Unit
IM 972-1 Maverick I Commercial Packaged Rooftop System: 15 to 25 Tons - (15,822KB) (Pub: 2011/09/08)
Models:MPSMaverick I Heating and Cooling units, Models MPS015B through 025B, 15 to 25 tons.Unit
IM 991 Maverick II Commercial Packaged Rooftop System MPS 062E - 075E - (6,455KB) (Pub: 2009/06/26)
Models:MPSModels MPS062E - MPS075E, 62 to 75 tons, R410 Refrigerant and MicroTech III Unit Controller. #AAIM991ZZControl
IM 1000-1 Maverick I Commercial Rooftop with BACnet Comm Module - (1,575KB) (Pub: 2011/06/07)
Models:MPSinstallation manual for the Maverick I commercial rooftop unit controller with BACnet communication module.Control
IM 1005-2 MicroTech® III Remote User Interface - (538KB) (Pub: 2012/04/23)
Models:AGZ,AWS,DPS,MPS,RAH,RDE,RDS,RDT,RFS,RPE,SWP,SWTInstallation and maintenance manual for the MicroTech III remote user interface. Used with RoofPak, Maverick II and Rebel rooftop units; Self Contained Units; Pathfinder Chillers and Air Cooled Scroll Model AGSD Chillers.Control
IM 1133 DIII-NET Communication Gateway for DOAS VRV Systems - (1,634KB) (Pub: 2011/09/19)
Models:MPS,RAH,RDT,RPS,SWP,SWTThe DIII-NET Communication Gateway is used for McQuay MicroTech III packaged air conditioners with a Daikin VRV System. Applies to RoofPak and Maverick II rooftops.Control
IM 916-3 MicroTech III Rooftop and Self Contained BACnet IP Comm Module - (346KB) (Pub: 2012/04/24)
Models:DPS,MPS,RAH,RCS,RDE,RDS,RDT,RFS,RPE,RPSInstallation manual for the BACnet IP communication module used with the MicroTech III Rooftop and Self Contained Unit Controller. Applied to Applied Rooftop and Maverick II commercial Rooftop units, as well as to Self Contained units.Control
IM 917-2 BACnet MS-TP Communication Module for MicroTech III Rooftop and Self Contained - (443KB) (Pub: 2012/04/24)
Models:DPS,MPS,RAH,RCS,RDE,RDS,RDT,RFS,RPE,RPSInstallation manual for the BACnet MS-TP communication module for Rooftop and Self Contained units with the MicroTech III Unit ControllerControl
IM 918-2 LonWorks Communication Module for MicroTech III Rooftop and Self Contained - (365KB) (Pub: 2012/04/24)
Models:DPS,MPS,RAH,RCS,RDE,RDS,RDT,RPE,RPS,SWP,SWTInstallation manual for the LonWorks Communication Module for the the Rooftop and Self Contained units with the MicroTech III unit controller. This comm module can be used on Applied and Commercial rooftop units as well as Self Contained units.Control
IM 919-1 MicroTech III Unit Controller for Commercial Rootop, Applied Rooftop and Self-Contained Systems - (4,123KB) (Pub: 2010/06/02)
Models:MPS,RAH,RDS,RDT,RFS,RPS,SWP,SWTModels MPS, RAH, RDS, RDT, RFS, RPS, SWP, and SWTControl
IM 999-1 Maverick I Commercial Rooftop with LonWorks SCC Module - (1,169KB) (Pub: 2011/06/07)
Models:MPSinstallation manual on the Maverick I commercial rooftop unit controller with LonWorks SCC communication module.Control
OM 844-5 MD2 Variable Speed Drive Controller - (2,104KB) (Pub: 2011/06/01)
Models:CAC,CAH,LHA,MPS,OAC,OAH,RAH,RDE,RDS,RFS,RPE,RPS,SWP,SWTPackaged Rooftop Units RPS/RFS/RDT/RPE/RDE, Rooftop Air Handler Units RDS/RAH, Indoor and Outdoor Air Handler Units LAH/CAC/CAH/OAC/OAH, Vertical Self-Contained Units SWP/SWT, Commercial Packaged Rooftop Units MPS (15 - 75 ton)Control
OM 920-3 MicroTech III Unit Controller for Commercial Rootop, Applied Rooftop and Self-Contained Systems - (786KB) (Pub: 2010/08/02)
Models:MPS,RAH,RCS,RDS,RDT,RFS,RPS,SWP,SWTModels MPS, RAH, RCS, RDS, RDT, RFS, RPS, SWP, and SWTAccessory
IM 904 Disconnect Switch for Maverick I Units - (238KB) (Pub: 2008/01/07)
Models:MPSMPS - Disconnect switch for Maverick I Units. Part #AAIM904ZZ.Accessory
IM 905 GFCI Convenience Outlet for Maverick I Units - (247KB) (Pub: 2008/01/07)
Models:MPSMPS - convenience outlet for Maverick I Units. Part #AAIM905ZZ.Accessory
IM 908 Smoke Detector for Maverick Units - (203KB) (Pub: 2008/01/07)
Models:MPSMPS - smoke detector for Maverick Units. Part #AAIM908ZZ.Accessory
IM 921-1 Accessories for Maverick I Commercial Packaged Rooftop Systems - (10,389KB) (Pub: 2010/05/05)
Models:MPSelectronic copy only. Models MPS003 through MPS025, 3 - 25 tons with R-410A refrigerant
OM 895-1 MD3 600 Volt Variable Speed Drive Controllers - (2,796KB) (Pub: 2010/11/08)
Models:LAH,MPS,OAH,RAH,RDE,RDS,RDT,RFS,RPE,RPSPackaged Rooftop Units: MPS, RPS, RFS, RDT, RPE, RDE - Rooftop Air Handler Units: RDS, RAH - Vision Indoor Air Handler Units - Skyline Outdoor Air Handler Units - Vertical Self-Contained Units: SWP, SWT
Unit
Maverick I Rooftop Units Physical Data - (562KB) (Pub: 2010/02/01)
Models:MPSMaverick I units 3 to 25 tonsUnit
Maverick II Rootop Units Physical Data - (656KB) (Pub: 2010/02/01)
Models:MPSMaverick II units - 15 to 75 tons
Unit
Replacement Parts List: 7000084 - (922KB) (Pub: 2011/12/15)
Models:MPSRPL: MPS 030-050 Vintage A,E; Maverick II Packaged Rooftop, Cooling & HeatingUnit
Replacement Parts List: 7000149 - (574KB) (Pub: 2011/12/15)
Models:MPSRPL: MPS 020-025 Vintage E, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 7000155 - (1,166KB) (Pub: 2012/01/20)
Models:MPSRPL: MPS 020-025 Vintage F, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 7000158 - (1,473KB) (Pub: 2011/12/15)
Models:MPSRPL: MPS 062-075 Vintage E, R410A, Maverick II, Packaged Rooftop UnitUnit
Replacement Parts List: 7000159 - (1,169KB) (Pub: 2012/01/20)
Models:MPSRPL: MPS 015-017 Vintage F, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 7000160 - (1,982KB) (Pub: 2011/12/15)
Models:MPSRPL: MPS 030-050 Vintage F, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 7000210 - (1,351KB) (Pub: 2012/04/13)
Models:MPSRPL: MPS 020 Vintage G, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 7000232 - (1,551KB) (Pub: 2012/01/20)
Models:MPSRPL: MPS 026 Vintage G, R410A, Maverick II Commercial Packaged Rooftop Cooling and HeatingUnit
Replacement Parts List: 92-42807-MPS003-005AG - (660KB) (Pub: 2011/06/03)
Models:MPSRPL: MPS 003-005AG, Maverick I Packaged Rooftop, Gas Heat, R22Unit
Replacement Parts List: 92-42807-MPS003-005AY - (574KB) (Pub: 2011/08/26)
Models:MPSRPL: MPS 003-005AY, Maverick I Packaged Rooftop, Cool Only or Clg with Electr Heat, R22Unit
Replacement Parts List: 92-42807-MPS003-005BG - (748KB) (Pub: 2012/04/30)
Models:MPSRPL: MPS 003-005BG, Maverick I Packaged Rooftop, R410a, Gas HeatUnit
Replacement Parts List: 92-42807-MPS003-005BY - (604KB) (Pub: 2012/01/27)
Models:MPSRPL: MPS 003-005BY, Maverick I Packaged Rooftop, R410a, Cooling OnlyUnit
Replacement Parts List: 92-42807-MPS003-025BG-D - (2,040KB) (Pub: 2012/03/02)
Models:MPSRPL: MPS 003-025BG(D), Maverick Rooftop, R410a, Gas Heat, DDC ControlsUnit
Replacement Parts List: 92-42807-MPS003-025BY-D - (1,677KB) (Pub: 2012/03/02)
Models:MPSRPL: MPS 003-025BY(D), Maverick Rooftop, R410a, Cooling Only, DDC ControlsUnit
Replacement Parts List: 92-42807-MPS006-025BG - (1,343KB) (Pub: 2012/03/02)
Models:MPSRPL: MPS 006-025BG, Maverick Rooftop, R410a, Gas HeatUnit
Replacement Parts List: 92-42807-MPS006-025BY - (1,226KB) (Pub: 2012/03/02)
Models:MPSRPL: MPS 006-025BY, Maverick I Packaged Rooftop, R410a, Cooling OnlyUnit
Replacement Parts List: 92-42807-MPS006AG - (634KB) (Pub: 2010/09/23)
Models:MPSRPL: MPS 006AG, Maverick I Packaged Rooftop, Gas Heat, R22Unit
Replacement Parts List: 92-42807-MPS006AY - (463KB) (Pub: 2010/09/23)
Models:MPSRPL: MPS 006AY, Maverick I Packaged Rooftop, Cool Only or Cooling w/Electr Heat, R22Unit
Replacement Parts List: 92-42807-MPS007-020AG - (781KB) (Pub: 2012/01/27)
Models:MPSRPL: MPS 007-020AG, Maverick I Packaged Rooftop, Gas Heat, R22Unit
Replacement Parts List: 92-42807-MPS007-020AY - (827KB) (Pub: 2012/01/27)
Models:MPSRPL: MPS 007-020AY, Maverick I Packaged Rooftop, Cool Only or Htg & Clg, Electric/Electric, R22Unit
Replacement Parts List: 92-42807-MPSH03-H05BG-D - (716KB) (Pub: 2012/01/20)
Models:MPSRPL: MPS H03-H05BG(D), Maverick Rooftop, High Efficiency, R410a, Gas Heat, DDC ControlsUnit
Replacement Parts List: 92-42807-MPSH03-H05BY-D - (622KB) (Pub: 2012/01/20)
Models:MPSRPL: MPS H03-H05BY(D), Maverick Rooftop, High Efficiency, R410a, Cooling Only, DDC Controls
Unit
McQuay_Revit_2010_-_Commercial_Packaged_RTU_Maverick_MPS.zip - (14.7MB) (Pub: 2012/03/12)
Models:MPSRevit 2010 content for commercial packaged rooftop model MPS, Maverick I and Maverick II R-410A units. Maverick I units are 3 - 25 ton. Maverick II units are 15 - 50 ton.